| General specifications |
| Signal type | Analog output |
| Functional safety related parameters |
| Safety Integrity Level (SIL) | SIL 2 |
| Supply |
| Connection | Power Rail or terminals 7 , 8- |
| Rated voltage | 20 ... 35 V DC |
| Ripple | within the supply tolerance |
| Rated current | current output: ≤ 50 mA ; voltage output: ≤ 20 mA |
| Power dissipation | 1.2 W |
| Input |
| Connection side | control side |
| Connection | terminals 9 , 10-, 11 |
| Voltage drop | optional current input: approx. 4 V at 20 mA |
| Input current | ≤ 100 ?A up to 50 ?C (122 ?F) at 10 V |
| Limit | optional current input: Input current: approx. ≤40 mA optional voltage input: input voltage: 12 V DC |
| Transmission range | optional current input: 0 ... 20 mA/optional voltage input: 0 ... 10 V |
| Output |
| Connection side | field side |
| Connection | terminals 1 , 2- |
| Current | optional current output: 0 ... 20 mA/optional voltage output: ≤ 20 mA |
| Load | optional current output: max. 850 Ω
optional voltage output: output resistance max. 3 Ω |
| Voltage | optional current output: 17 V at 20 mA/optional voltage output: 0 ... 10 V |
| Transfer characteristics |
| Accuracy | 0.1 % |
| Rise time | < 10 ms |
| Indicators/settings |
| Display elements | LED |
| Labeling | space for labeling at the front |
| Directive conformity |
| Electromagnetic compatibility | |
| | Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
| Conformity |
| Degree of protection | IEC 60529:2001 |
| Ambient conditions |
| Ambient temperature | -20 ... 60 ?C (-4 ... 140 ?F) |
| Mechanical specifications |
| Degree of protection | IP20 |
| Connection | screw terminals |
| Mass | approx. 100 g |
| Dimensions | 20 x 107 x 115 mm (0.8 x 4.2 x 4.5 inch) , housing type B1 |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
| Data for application in connection with hazardous areas |
| EU-Type Examination Certificate | BAS 02 ATEX 7203 |
| | Marking |

II (1)G [Ex ia Ga] IIC ,

II (1)D [Ex ia Da] IIIC ,

I (M1) [Ex ia Ma] I |
| Certificate | T?V 99 ATEX 1499 X |
| | Marking |

II 3G Ex nA II T4 |
| Directive conformity | |
| | Directive 2014/34/EU | EN 60079-0:2012 A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 |
| International approvals |
| FM approval | |
| | Control drawing | 116-0129 |
| UL approval | |
| | Control drawing | 116-0173 (cULus) |
| IECEx approval | IECEx BAS 05.0041
|
| | Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I |